CES-I-BP-U-C07-SI-162815 (Order no. 162815)

Safety switch CES-I-BP-.-C07-..., RFID, plug connector(s) M12, for connection to decentralized peripheral systems

  • Unicode
  • M12 plug connector(s), 5-pin, pin 5 not assigned
  • for connection to decentralized peripheral systems
CES-I-BP-U-C07-SI-162815 (Order no. 162815)

Description

Direct connection to decentralized peripheral systems

The connection via M12 plug connector(s) is optimized for direct connection to IP67 IO modules, such as ET200pro and ET200eco from SIEMENS, MVK from MURR and EP1957 from BECKHOFF.

Approach direction and installation position

Permissible installation position

Typical operating distance

(Only in conjunction with actuator CES-A-BTN-C07)

For a side approach direction for the actuator and safety switch, a minimum distance of s = 6 mm must be maintained so that the actuating range of the side lobes is not entered.

Attention:

The actuating range may vary depending on the actuator, substrate material and installation situation. Further actuating ranges can be found in the operating instructions.

Unicode evaluation

Each actuator is highly coded (unicode). The switch detects only taught-in actuators. Additional actuators can be taught-in.

Only the last actuator taught-in is detected.

Safety characteristics

Thanks to two redundant safety outputs (semiconductor outputs) with internal monitoring, the device is suitable for:

  • Category 4 /PL e according to EN 13849-1
  • SIL 3 according to EN IEC 62061

The OSSD outputs used check their function for short circuits and short circuits with test pulses.

LED indicator

STATE

Status LED

DIA

Diagnostics LED

Terminal assignment

Plug connector (view of connection side)PinDesignationFunctionConnecting cable conductor coloring

1UBPower supply, DC 24 VBN
2FO1ASafety output, channel AWH
30 VGround, DC 0 VBU
4FO1BSafety output, channel BBK
5-n.c.GY

Plug connector(s) adjusted C07

The following applies for the installation position of the device shown: cable outlet C (left), cable outlet A (right).

Scope of delivery

  • Cover caps for the mounting holes

Accessories required

Dimension drawing
Dimension drawing
Wiring diagram
Wiring diagram
CES-C07: Transponder-coded safety switch

Dimensional drawings

Dimensional drawings
1LEDs
2Active face
3With the installation orientation shown: cable outlet on left or right

Connection examples

Connection examples

Technical data

Approvals

EAC_RU C-DE.MO05.B.00971/20TUEV Süd München_Z10 040393 0031 Rev. 02c_UL_us_E346349_1/1FCC_2AJ58-12_ECOLAB__CES C07

Workspace

Repeat accuracy R 10 %

Electrical connection values

Fuse
external (operating voltage) 0.25 ... 8 A
rated conditional short-circuit current 100 A
Rated insulation voltage Ui 75 V
Rated impulse voltage Uimp 1.5 kV
Operating voltage DC
UB 24 V DC -15% ... +15% regulated, residual ripple<5%, PELV
Turn-on time
Safety outputs max. 100 ms
EMC protection requirements Acc. to EN IEC 60947-5-3
Risk time according to EN 60947-5-3 max. 125 ms
Safety class III
Current consumption 40 mA
Degree of contamination (external, according to EN 60947-1) 3
Monitoring output OD/C
Output type p-switching, short circuit-proof
Output voltage UB-1.5 ... UB V DC
Switching current 1 ... 50 mA
Safety outputs FO1A/FO1B
Output type Semiconductor outputs, p-switching, short circuit-proof
Output voltage
HIGH U(FO1A) / U(FO1B) UB-1.5V ... UB V DC (Values at a switching current of 50 mA without taking into account the cable lengths.)
LOW U(FO1A) / U(FO1B) 0 ... 1 V DC
Discrepancy time max. 10 ms
Utilization category
DC-13 24V 150mA (Caution: outputs must be protected with a free-wheeling diode in case of inductive loads.)
Off-state current Ir max. 0.25 mA
Switching current 1 ... 150 mA
Test pulse duration 0.3 ms (Applies to a load with C<= 30nF and R<= 20kOhm)
Test pulse interval ca 100 ms

Mechanical values and environment

Dimensions 40 x 26.5 x 18
Connection type M12 plug connector, 5-pin
Tightening torque max. 0.8 Nm
Ready delay 5 s
Operating altitude max. 4 000 m
Installation orientation any
Switching frequency max. 1 Hz
Mounting distance
between switches min. 50 mm
Mounting type Surface mounting on metal
Shock and vibration resistance Acc. to EN IEC 60947-5-3
Degree of protection IP65/IP67/IP69/IP69K
Ambient temperature
at UB = 24 V DC -25 ... 55 °C (+65 °C at IL = max. 10 mA per safety output)
Material
Housing Plastic, PBT-PC-GF30

Characteristic values according to EN ISO 13849-1 and EN IEC 62061

PLMaximum SILPFHDCategoryMission time
Monitoring of the guard positionPL e36x10-10420 y


Miscellaneous

Notices for UL approval Operation only with UL Class 2 power supply or equivalent measures
Additional feature Caps included

In combination with actuator CES-A-BDN-06-158210, CES-A-BTN-C07-156230

Switching hysteresis 1 ... 2 mm

In combination with actuator CES-A-BDN-06-158210

Switch-on distance
Installation position C 8 mm
Installation position D 7 mm
Installation position A 16 mm
Installation position B 11 mm
Secured switch-off distance sar
in x direction/installation position A max. 24 mm
in x direction/installation position C max. 21 mm
Secured switching distance sao
in x direction/installation position C min. 6 mm
in x direction/installation position A min. 13 mm

In combination with actuator CES-A-BTN-C07-156230

Switch-on distance
Installation position C + D 7 mm
Installation position A + B 13 mm
Secured switch-off distance sar
in x direction/installation position A + B max. 20 mm
in x direction/installation position C + D max. 17 mm
Secured switching distance sao
in x direction/installation position C min. 3 mm
in x direction/installation position B min. 9 mm
in x direction/installation position A min. 10 mm
in x direction/installation position D min. 2 mm

Accessories

Downloads

Complete package

Download all important documents with a single click.

Content:

  • The operating instructions and any additions to the operating instructions or brief instructions
  • Any data sheets to supplement the operating instructions
  • The declaration of conformity
Download Complete Package (ZIP, 4,1 MB)

Single Documents

Other Documents

Ordering data

Ordernumber 162815
Item designation CES-I-BP-U-C07-SI-162815
Gross weight 0,05kg
Customs tariff number 85365019000
ECLASS 27-27-24-03 Safety-related transponder switch